The hydraulic balance device is reasonably set in the heating and air conditioning water system. This is a new solution and effective technical measures to solve the system hydraulic imbalance, reduce system energy consumption, create a comfortable artificial environment. The setting principles are as follows:
(1)For a constant flow system, the designer should first achieve the hydraulic balance of each loop through the piping and system design, that is, “design balance”. When it is impossible to achieve "design balance" due to pipe diameter, flow rate, etc., static (manual) hydraulic balance valve should be considered to achieve hydraulic balance by initial adjustment. When the design thinks that the system may be caused by operation and management reasons (such as the change of the number of pumps running, etc.), it may cause a large fluctuation of water volume. It is better to use a dynamic flow balance valve with higher valve authority and higher resistance (also called self-power). Flow control valve).
(2)For the variable flow system, except for some places requiring specific flow rate (for example, in order to protect the normal operation of specific equipment or special requirements), dynamic flow balance valve should not be installed in the system, but dynamic pressure difference control valve (also known as self-operated pressure difference control valve and pressure difference regulator).
(3)Except for the small-scale heating system, which can satisfy the hydraulic balance by calculation, the outdoor heating pipeline is generally longer and the calculation is not easy to achieve the hydraulic balance. In order to avoid hydraulic imbalance caused by improper design, static hydraulic balancing valves should be installed at the thermal entrance of buildings in general heating systems, and dynamic flow balancing valves (for fixed flow water systems) or dynamic pressure difference control valves (for variable flow water systems) should be set up according to hydraulic calculation and the regulation methods adopted by heating systems in buildings. Otherwise, the imbalance problem will not be adjusted. Century Star introduced that dynamic flow balance valve should be installed at the thermal entrance of indoor vertical single-pipe spanning heating system when it needs to be set up after hydraulic calculation. For indoor double-pipe heating system, dynamic differential pressure control valve should be installed at its thermal inlet.
(4)The dynamic balance electric regulating valve should be installed in the water supply and return pipeline of combined air conditioner and fresh air unit. The valve has better regulating performance than the ordinary electric regulating valve.
Related News
  • Classification of Dirt Separator

    Classification of Dirt Separator

    May 28, 2019Pipeline dirt separator is also called pipeline filter, dirt separator. According to the different pipelines, it can be divided into vertical and horizontal dirt separators, Vertical filters can be di...view
  • Structure and Principle of Concentric Butterfly Valve

    Structure and Principle of Concentric Butterfly Valve

    April 4, 2019Butterfly valves, also known as flip valves, are often used in pipelines conveying various corrosive and non-corrosive fluids in engineering systems such as generators, gas, natural gas, liquefied pet...view
  • Careful Selection Of Fire Protection Non Slam Check Valve

    Careful Selection Of Fire Protection Non Slam Check Valve

    July 17, 2019ZECO Valve Group tells you that flue is inseparable from our life and is a necessity of our modern urban life. The flue fire non slam check valve is suitable for installing in the kitchen common ...view
  • The generation and application of flange butterfly valve

    The generation and application of flange butterfly valve

    April 4, 2019The development of butterfly valve flange has a forward-looking step as China's development. China's advancement is our constant pursuit and hard work. As for the development of China, the development...view
  • TEL:+86-21-59599006
  • FAX:+86-21-59599006 ext.806
  • EMAIL: marketing@zecovalve.com
  • ADDRESS:Caoan Road 3999#, Shanghai, China
ZECO Valve Product Information Catalog Download